Basic Info.
Model NO. MOT500-A-CH4S
Power 24VDC
Explosion Proof Sign Exdll CT4 (Ia)
Display LCD Displayed
Sampling Diffusion
Relay Output 2-3 Relays Output
Operating Pressure 0-200kpa
IP Rating IP 66
Modbus Digital Output RS485 Output
Material Aluminum,Explosion and Corrosion Proof
Analog Digital Output 4-20mA Output(0-5V,0-10V Optional)
Transport Package Standard Carton Packaging 26*21*14cm
Specification Product size: 20*17*8cm
Trademark Korno or customized
Origin China
HS Code 9027100090
Production Capacity 10000pieces/Month
Product Description
Online CH4S Gas leak detector/ Methyl Mercaptan Detetcor/ CH4S gas monitor
>>> Key Feature
1)2.4 inches technical grade display with a pixel up to 320*2402)Three concentration units are available PPM,%VOL,mg/m33)Variety signal output model : 4-20mA signal :Standard 16bit 4-20mA output chip, transmission distance 1Km RS485 signal: Standard MODBUS RTU protocol, transmission distance 2Km 2 relays output: Concentration alarm value adjustable, there are high alarm and low alarm respectively 0-5V,0-10V output(optional)4) Variety signal transmission are available :3-4 core cable,Optical fiber network,Network cable,3G transmission,Wireless transmission,Video transmission5).All software automatic calibration, sensor up to 6 level target calibration,ensure the accuracy and linearity of the full scale6) Chinese and English operation model are available,user friendly ,four buttons to operation7)Following function are optional:Temperature,Humidity sensor,Audible and visual alarm

Online CH4s Gas Leak Detector/ Methyl Mercaptan Detetcor/ CH4s Gas Monitor



>>> Specifications
Product Type:Online, Methyl Mercaptan(CH4S)
Sensor:Electrochemical Gas sensor
Detection Pattern:Diffusion,pipeline(screw thread size:M40*1.5MM),Circulation,Pumping is available,Online detection
Detection Range:0-10, 100, 200PPM
Resolution:0.01PPM
Detection Accuracy:≤±3%F.SLinearity error:≤±1%F.S
Reaction Time:≤20S(T90)Zero drift:≤±1%(F.S/Year)
Recovery Time:≤20SRepeatability:≤±1%F.S
Relay output:Two relays output,Contact rating:24VDC 3A/220VAC 3A
Explosion Proof Sign:ExdII CT6,Certification Number of Explosion-proof :CNEx10.1807
Outputs: Analog:4-20mA signal,0-5V,0-10V Modbus: RS485 signal Pulse signal or TCP/IP signal,optional
Alarm Setting:Two alarm set pointsAlarm mode optional: Low alarm-High alarm / High alarm-High alarm / Low alarm-Low alarm
Controllers:Compatible with DN1000, as well as most DCS/PLC systems
IP Rating :IP66
Material:Aluminum,Explosion and corrosion proofConnection:3/4″NPT,1/2″NPT
Dimensions:200×160×80mm(L×W×H)Weight:1.5 Kg(Net weight)
OperatingTemperature:-30 ~ 60ºCRelative Humidity:≤90%RH,Non-condensing
OperatingPressure:0 ~ 200KpaOperating Voltage:24VDC(9~30VDC)
Standard Accessories:-User manual-Certification-Calibration cover
Optional Accessories:-hose(5*8mm),drying tube,water separator or pumping pump-infrared remote control-temperature and humidity sensor,SMS alarm,3G module or wireless transmission module

>>> Details

Online CH4s Gas Leak Detector/ Methyl Mercaptan Detetcor/ CH4s Gas Monitor


>>> Customize Service
1) Show your company name and logo at the boot interface2) Print your company name,information,logo at the label and manual 3) Design stainless steel nameplate with your company name for free(≥20PCS)4) We can also silk-printing your Logo,design another color of the case for you if you have a large order.For more details,please contact us^ ^